Pepperl+Fuchs WHA-ADP2-F8B2 Z1 Series Manual page 53

Wirelesshart adapter
Table of Contents

Advertisement

WHA-ADP2-F8B2-*-**-Z1(-EX1)
Configuration
Figure 5.11
Event Tab
Parameter
Event Notification
Control Code
Device Index
Event Notification
Retry Time
Maximum Update
Time
Event Debounce
Interval
Event Status
First unACK Time Indicates the time in seconds an event notification has
Event notification, tab Event
Description
Switches event notification on or off ("Wireless" = on).
The following parameters in this table can only be edited if
Event Notification Control Code is set to "Wireless".
Otherwise they are grayed out.
Selects the device via its long tag for which the burst mode
applies.
<Adapter Long Tag>: Adapter parameters are transmitted.
<Device Long Tag>: Device parameters are transmitted.
For HART devices of Revision 5 or lower, the "Message"
serves as the long tag (see chapter 4.1).
Period between retransmissions of the event notification. The
event notification continues to be retransmitted until
anacknowledgement of the event is received.
Maximum period in seconds that may elapse between
successive event notifications. If no event occurs, the adapter
will publish an event notification after this time has elapsed.
The amount of time that a condition must persist before the
event notification is sent out.
Indicates whether a particular event notification has been sent
and is still unacknowledged.
Configuration Changed Event pending
Device Status Event Pending
More Status Available Event Pending
remained unacknowledged.
Default
Off
00:30:00
00:30:00
00:30:00
53