Pepperl+Fuchs WHA-ADP2-F8B2 Z1 Series Manual page 57

Wirelesshart adapter
Table of Contents

Advertisement

WHA-ADP2-F8B2-*-**-Z1(-EX1)
Configuration
Power Supply Parameters
Parameter
Power mode
Field Device Table Displays the parameters read from the HART device by the
Apply field device
power values
Start-Up Voltage
Start-Up Time
Start-Up Current
Operating Voltage Voltage connected device requires in normal operation.
Lead Time
Description
Sets the power mode.
"Off": Power to any connected device is switched off.
There is no communication between adapter and any
connected device. Set this mode if the adapter is to be
used as a router.
"Automatic": The connected device is powered-up when
an external master starts communicating with the adapter.
The device is powered after the last command for a period
determined by "Power On Time After External Trigger".
"Configuration": The connected device is powered-up
when the button on the adapter is pressed or an external
master communicates with it. The device is powered after
the last command for a period determined by
"Configuration Time". When this period has elapsed, the
power mode reverts to "Automatic"
scan:
Manufacturer ID: Manufacturer of connected device
Expanded Device Type Code: Device identifier as per
HART
Device ID: Manufacturer's device identifier
Universal Command Revision Level: HART revision
supported
Long Tag: Long tag of device (Message for HART revision
< 6.0)
* Start-Up Voltage: Voltage required to start the connected
device
* Start-Up Time: Time required for the device to wake-up
* Start-Up Current: Current consumed on starting the
device
* Lead Time: Time that elapses between start-up and the
point when the HART communication is synchonized
* Parameters taken from DTM
Press this button to apply the field device power values.
Voltage required by the connected device on start up.
Valid range 8 ... 23 V in steps of 0.1 V.
Filled automatically if the Field Device table is active.
Time in seconds required for the device to start up.
Filled automatically if the Field Device table is active.
Current in mA drawn by the connected device during start-up.
Filled automatically if the Field Device table is active.
Filled automatically if the Field Device table is active.
Time that elapses between start-up and the point at which the
device can deliver valid values.
Filled automatically if the Field Device table is active.
Default
Confi-
guration
16
5
14
16
10
57