Alcatel-Lucent 1677 SONET Link Manual page 193

Turn-up
Hide thumbs Also See for 1677 SONET Link:
Table of Contents

Advertisement

3EM13850AD
Issue 01, September 2007
Are there errors?
76
Record verification in CKL-115.
77
Enter
78
Enter
79
Observe output. Is CCC in slot 9 IS,STBYH and CCC in slot 10 IS,WRK.
80
Enter
81
Enter
82
Enter
83
Did CCCs change states (CCC in slot 9 is IS,WRK and CCC in slot 10 is IS,STBYH)?
84
Refer to 1677 SONET Link Maintenance and Trouble Clearing manual
85
(PN 3EM13853AF) to clear trouble.
Is trouble cleared?
86
Are errors reported?
87
Refer to 1677 SONET Link Maintenance and Trouble Clearing manual
88
(PN 3EM13853AF) to determine source of error before going to next step.
Reset test set error count to zero and monitor for 10 seconds.
89
Verify Clock and Control Subsystem Switching
If yes, go to step 72.
If no, go to step 77.
to retrieve equipment parameters of copy 0 CCC.
RTRV-EQPT::CCC-9;
RTRV-EQPT::CCC-10;
If yes, go to step 81.
If no, refer to DLP-122, then go to step 78.
SW-DX-EQPT::CCC-10;
RTRV-EQPT::CCC-10;
RTRV-EQPT::CCC-9;
If yes, go to step 87.
If no, go to step 85.
If yes, go to step 78.
If no, go to step 85.
If yes, go to step 88.
If no, record information in CKL-115, then go to step 91.
to retrieve equipment parameters of copy 1 CCC.
DLP-125
4-149