System Electrical Specifications - Huawei UPS5000-E-60K-F60 User Manual

Hide thumbs Also See for UPS5000-E-60K-F60:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-160 kVA)
User Manual (Low Voltage)
Item
Overload
capability

8.8 System Electrical Specifications

Item
Redundan
cy design
Number
of parallel
UPSs
Issue 05 (2024-01-30)
Specifications
Inverter overload capability:
● 105% < load ≤ 110%: transfers to bypass mode after 60
min
● 110% < load ≤ 125%: transfers to bypass mode after 10
min
● 125% < load ≤ 150%: transfers to bypass mode after 1 min
Bypass overload capability:
● Load ≤ 135%: runs continuously in bypass mode at 30°C or
less
● 1000% load: runs for 100 ms
Specifications
The auxiliary power supplies, centralized controllers, and parallel
signals use redundancy design.
2
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 Technical Specifications
219