System Electrical Specifications - Huawei UPS5000-A User Manual

Hide thumbs Also See for UPS5000-A:
Table of Contents

Advertisement

UPS5000-A-(30 kVA-120 kVA) User Manual
User Manual
Item
Specifications
Inverter
● UPS5000-A-30KTTL/UPS5000-A-40KTTL/UPS5000-A-80KTTL/UPS5000-
overload
A-60KTTL/UPS5000-A-120KTTL:
capability
– 100% < load ≤ 110%: transfer to bypass mode after 60 min
– 110% < load ≤ 125%: transfer to bypass mode after 10 min
– 125% < load ≤ 150%: transfer to bypass mode after 1 min
– Load > 150% or a short circuit occurs: run for 200 ms
● UPS5000-A-60KTTL-H/UPS5000-A-120KTTL-H:
– 100% < linear load ≤ 110%: transfer to bypass mode after 60 min
– 110% < linear load ≤ 125%:
– 125% < load ≤ 150%: transfer to bypass mode after 30s
– Load > 150% or a short circuit occurs: run for 200 ms

8.9 System Electrical Specifications

Item
Parallel system
reliability
ECO function
No-load loss
Number of parallel
UPSs
Power distribution
system
Issue 15 (2022-11-15)
– 0–30°C: transfer to bypass mode after 10 min
– 30–40°C: transfer to bypass mode after 3 min
Specifications
Redundancy design for parallel signals
Supported
● UPS5000-A-30KTTL (BOM number: 02291114), UPS5000-A-40KTTL
(BOM number: 02291115), and UPS5000-A-60KTTL-H: 1.5 kW
● UPS5000-A-120KTTL-H: 2 kW
● PS5000-A-30KTTL (BOM number: 02290371), UPS5000-A-40KTTL
(BOM number: 02290372), UPS5000-A-80KTTL, and UPS5000-
A-120KTTL: < 2 kW
A maximum of four UPSs can be connected in parallel.
TN-C, TN-S, TN-C-S, TT
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 Technical Specifications
151