7.7.2.1
Changing over the motor standard
You change over the motor standard using p0100. The following applies:
● p0100 = 0: IEC motor (50 Hz, SI units)
● p0100 = 1: NEMA motor (60 Hz, US units)
● p0100 = 2: NEMA motor (60 Hz, SI units)
The parameters listed below are affected by the changeover.
Table 7- 24
P no.
r0206
p0307
p0316
r0333
p0341
p0344
r1969
*) Factory setting
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
Variables affected by changing over the motor standard
Designation
Power Module rated power
Rated motor power
Motor torque constant
Rated motor torque
Motor moment of inertia
Motor weight (for thermal motor type)
Speed_cont_opt moment of inertia determined
Advanced commissioning
7.7 Application-specific functions
Unit for p0100 =
0*
1
)
kW
HP
kW
HP
Nm/A
lbf ft/A
Nm
lbf ft
kgm
lb ft
2
2
kg
Lb
kgm
lb ft
2
2
2
kW
kW
Nm/A
Nm
kgm
2
kg
kgm
2
177