Feeder Protection Of Individual Inverters - Siemens SINAMICS G120D Series Operating Instructions Manual

Distributed converter, control units cu240d-2 with encoder evaluation.
Hide thumbs Also See for SINAMICS G120D Series:
Table of Contents

Advertisement

4.2.4

Feeder protection of individual inverters

If you install a separate 400-V feeder for each inverter, you must protect each feeder
individually.
Figure 4-5
Feeder protection according to IEC
Table 4- 1
Rated power
0.75 kW
1.5 kW
3 kW
4 kW
5.5 kW
7.5 kW
Feeder protection according to UL standards
Use in North America requires protection devices that meet UL standards as detailed in the
following tables.
Table 4- 2
Protection device
Fuses of any manufacturer with faster tripping characteristic than class RK5, e.g.
class J, time, CC, G, or CF
SIEMENS circuit breaker
Intrinsically safe SIEMENS circuit breaker
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
Power supply to inverters through separate 400-V feeders
Feeder protection according to IEC
Power Module
6SL3525-0PE17-5AA1
6SL3525-0PE21-5AA1
6SL3525-0PE23-0AA1
6SL3525-0PE24-0AA1
6SL3525-0PE25-5AA1
6SL3525-0PE27-5AA1
Overview of the approved protection devices according to UL standards
Frame
Article No.
size
Fuse
Circuit-breaker
FSA
3NA3803
3RV2011-1JA10
FSB
3NA3805
3RV2011-4AA10
FSC
3NA3807
3RV2021-4BA10
3NA3812
3RV2021-4PA10
Installation
4.2 Electrical Installation
Max. rated
current of the
protection de-
vice
10 A
16 A
20 A
32 A
UL category
JDDZ
DIVQ
NKJH
35

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu240d-2 dpSinamics g120d cu240d-2 pn-f ppSinamics g120d cu240d-2 pn-f foSinamics g120d cu240d-2 dp-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-f

Table of Contents