Procedure with STARTER with enabled safety functions
To load the settings from the PG to the inverter with STARTER and to activate the safety
functions, proceed as follows:
1. Go online:
2. Click the "Download project to target system" button:
3. Call the STARTER screen form for the safety functions.
You have transferred the settings from the PG to the inverter.
To activate the safety functions, proceed as follows:
1. Select the "Copy parameter" button.
2. Press the "Activate settings" button.
3. To save the data in the inverter, click the "Copy RAM to ROM" button:
4. Go offline:
5. Switch off the inverter power supply.
6. Wait until all LEDs on the inverter go off.
7. Switch on the inverter power supply again. Your settings only become effective after this
power-on reset.
You have transferred the settings from the PG to the inverter with STARTER and activated
the safety functions.
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
8.2 Backing up and transferring settings using STARTER
.
.
Backing up data and series commissioning
.
.
227