Offset and page index of the parameter numbers
Parameter numbers < 2000
Parameter numbers ≥ 2000
Parameter number
0000 ... 1999
2000 ... 3999
6000 ... 7999
8000 ... 9999
10000 ... 11999
20000 ... 21999
30000 ... 31999
60000 ... 61999
Indexed parameters
For indexed parameters, you must write the index as hex value into the subindex (IND
bit 15 ... 8).
Parameter contents
Parameter contents can be parameter values or connectors.
Table 6- 5
Table 6- 6
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
PNU = parameter number.
Write the parameter number into the PNU (PKE bit 10 ... 0).
PNU = parameter number - offset.
Write the parameter number minus the offset into the PNU
(PKE bit 10 ... 0).
Write the offset in the page index (IND bit 7 ... 0).
Offset
Page index
Hex
0
0 hex
2000
80 hex
6000
90 hex
8000
20 hex
10000
A0 hex
20000
50 hex
30000
F0 hex
60000
74 hex
Parameter values in the parameter channel
PWE, 3rd word
Bit 15 ... 0
0
0
Connectors in the parameter channel
PWE, 3rd word
Bit 15 ... 0
Number of the connector
6.2 PROFIdrive profile for PROFIBUS and PROFINET
Bit 7
Bit 6
Bit 5
Bit 4
0
0
0
1
0
0
1
0
0
0
0
1
1
0
1
0
1
0
1
1
1
0
1
1
Bit 15 ... 8
0
32-bit value
Bit 15 ... 10
3F hex
Adapt fieldbus configuration
Bit 3
Bit 2
Bit 1
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
1
0
0
0
1
0
1
0
PWE, 4th word
Bit 7 ... 0
8-bit value
16-bit value
PWE, 4th word
Bit 9 ... 0
The index or bit field num-
ber of the connector
Bit 0
0
0
0
0
0
0
0
0
103