Alarms, faults and system messages
10.6 List of alarms and faults
Number
Cause
A07922
Torque/speed out of tolerance
F07923
Torque/speed too low
F07924
Torque/speed too high
A07927
DC braking active
A07980
Rotary measurement activated
A07981
No enabling for rotary measure-
ment
A07991
Motor data identification activated
F08501
Setpoint timeout
F08502
Monitoring time sign-of-life expired
F08510
Send configuration data not valid
A08511
Receive configuration data not
valid
A08526
No cyclic connection
A08565
Consistency error affecting adjust-
able parameters
F08700
Communications faulty
F13100
Know-how protection: Copy protec-
tion error
F13101
Know-how protection: Copy protec-
tion cannot be activated
278
Remedy
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
Not required
Not required
Acknowledge pending faults.
Establish missing enables (see r00002, r0046).
Switch on the motor and identify the motor data.
Check the PROFINET connection.
Set the controller to RUN mode.
If the error occurs repeatedly, check the set monitoring time p2044.
Check the PROFINET connection.
Check the PROFINET configuration
Activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
A CAN communications error has occurred. Check the following:
Bus cable
Baud rate (p8622)
Bit timing (p8623)
Masters
Start the CAN controller manually with p8608 = 1 after the cause of the
fault has been resolved!
The know-how protection and the copy protection for the memory card
are active. An error occurred during checking of the memory card.
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
Insert a valid memory card.