Technical data
11.9 Electromagnetic Compatibility
EMC Immunity
The SINAMICS G120D drives have been tested in accordance with the immunity
requirements of category C3 (industrial) environment:
Table 11- 9
EMC Phenomenon
Electrostatic Discharge (ESD)
Radio-frequency Electromagnet-
ic Field
Amplitude modulated
Fast Transient Bursts
Surge Voltage
1.2/50 μs
Conducted
Radio-frequency Common Mode
Mains Interruptions & Voltage
Dips
Voltage Distortion
Voltage Unbalance
Frequency Variation
Commutation Notches
Note
The immunity requirements apply equally to both filtered and unfiltered units.
292
EMC Immunity
Standard
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
EN 61000-2-4
EN 61000-2-4
EN 61000-2-4
EN 60146-1-1
Level
4 kV Contact discharge
8 kV Air discharge
80 MHz ... 1000 MHz
10 V/m
80 % AM at 1 kHz
2 kV @ 5 kHz
1 kV differential (L-L)
2 kV common (L-E)
0.15 MHz ... 80 MHz
10 V/rms
80 % AM at 1 kHz
95 % dip for 3 ms
30 % dip for 10 ms
60 % dip for 100 ms
95 % dip for 5000 ms
10 % THD
3 % Negative Phase Se-
quence
Nominal 50 Hz or 60 Hz
(± 4 %)
Depth = 40 %
Area = 250 % x degrees
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
Performance
Criterion
A
A
A
A
A
A
C
C
D
A
A
A
A