Backing up data and series commissioning
8.2 Backing up and transferring settings using STARTER
Procedure with Startdrive
To transfer the settings from the PG to the inverter with Startdrive and activate the safety
functions, proceed as follows:
1. Save the project.
2. Select "Load to device."
Figure 8-2
3. Connect Startdrive online with the drive.
4. Click the "Start safety commissioning" button.
5. Enter the password for the safety functions.
If the password is the factory default, you are prompted to change the password.
If you try to set a password that is not permissible, the old password will not be changed.
6. Click the "End safety commissioning" button.
7. Confirm the prompt for saving your settings (copy RAM to ROM).
8. Disconnect the online connection.
9. Switch off the inverter supply voltage.
10.Wait until all LEDs on the inverter go dark (no voltage condition).
11.Switch on the inverter supply voltage again.
You have transferred the settings from the PG to the inverter with Startdrive and have
activated the safety functions.
228
Activating settings in Startdrive
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB