Siemens SINAMICS G120D Series Operating Instructions Manual page 181

Distributed converter, control units cu240d-2 with encoder evaluation.
Hide thumbs Also See for SINAMICS G120D Series:
Table of Contents

Advertisement

DC braking when falling below a start speed
DC braking initiated using a control command
Precondition: p1231 = 4 and p1230 = control
command, e.g. p1230 = 722.3 (control command
DC braking when falling below a starting speed
1. The motor speed has exceeded the starting speed.
2. The inverter activates the DC braking as soon as the motor speed falls below the starting
speed.
DC braking when a fault occurs
1. A fault occurs, which initiates DC braking as response.
2. The motor brakes along the down ramp to the speed for the start of DC braking.
3. DC braking starts.
DC braking initiated by a control command
1. The higher-level control issues the command for DC braking, e.g. using DI3: p1230 =
722.3.
2. DC braking starts.
If the higher-level control withdraws the command during DC braking, the inverter interrupts
DC braking and the motor accelerates to its setpoint.
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
Precondition: p1230 = 1 and p1231 = 14
via DI 3)
Advanced commissioning
7.7 Application-specific functions
DC braking when a fault occurs
Precondition: Fault number and fault response
are assigned using p2100 and p2101
DC braking when switching off the motor
Precondition: p1231 = 5 or p1230 = 1 and p1231
= 14
181

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120d cu240d-2 dpSinamics g120d cu240d-2 pn-f ppSinamics g120d cu240d-2 pn-f foSinamics g120d cu240d-2 dp-fSinamics g120d cu240d-2 pnSinamics g120d cu240d-2 pn-f

Table of Contents