Changing Over To Setpoint Generator Operation; Checking The Actual Values - Siemens SIMOVERT MV Series Commissioning Instructions

Medium-voltage converters with hv-igbt and ihv filter
Table of Contents

Advertisement

P530
DP.PPR
4.3.2

Changing over to setpoint generator operation

Setpoint generator operation can only be implemented without the motor
connected or with the motor mechanically de-coupled from the load.
1. The drive converter must be powered-down.
2. Set B60.X / P432 to 4 in the FP-WRS.
3. Set SWG.IRM / P872 to 1 in the FP-TRV.
4. Enter 0 % setpoint at SWG30.X (FP-TRV).
5. Enter 0 % frequency setpoint at SWG50.X (FP-TRV).
6. Power-up the drive converter, enable the inverter.
7. Enter the current setpoint, e.g. 30 % at SWG30.X.
8. Enter the frequency setpoint, e.g. 10 % at SWG50.X.
Re-establish the original settings (undo the changes) after you have completed this
operation (inverse sequence).
4.3.3

Checking the actual values

In order to be able to check the actual values, the closed-loop control must be
changed-over into setpoint generator operation (refer to Section 4.3.2). The current
actual values I
terminals X2:3/4 and X2:5/6. In this case, in FP-TRC, the connector AUSW.IF must
be set to a logical 1, and in FP-TRV, the connector THEN27.IF must be set to a
logical 0. The currents I
display mode. Only a circle should be seen on the oscilloscope. At lower speeds,
the display may rotate in a counter-clockwise direction.
62
Pulse number per revolution
and I
can be tapped at the interface module -A132 (SU11),
A
B
and I
should be connected to an oscilloscope in the X-Y
A
B
Siemens AG
SIMOVERT MV
Commissioning Instructions
6SE8004-0BH76

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents