Backing up data and series commissioning
8.2 Backing up and transferring settings using STARTER
PC/PG → inverter
The procedure depends on whether you also transfer settings of safety functions or not.
Procedure with STARTER without enabled safety functions
To load the settings from the PG to the inverter with STARTER, proceed as follows:
1. Go online:
2. Click the "Download project to target system" button:
3. Wait until STARTER reports that loading has been completed.
4. To save the data to the non-volatile memory of the inverter, select the "Copy RAM to
ROM" button:
5. Go offline:
You have transferred the settings from the PG to the inverter with STARTER.
Procedure with Startdrive without enabled safety functions
To transfer the settings from the PG to the inverter with Startdrive, proceed as follows:
1. Go online.
2. Select "Load to device" > "Hardware and software" from the shortcut menu.
3. Wait until Startdrive reports that loading has been completed.
4. Go offline.
5. Confirm the dialog box that then opens by clicking "Yes" to save the data to the non-
volatile memory of the inverter (Copy from RAM to ROM).
You have transferred the settings from the PG to the inverter with Startdrive.
226
.
.
.
.
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB