Siemens SINAMICS G120D Series Operating Instructions Manual page 269

Distributed converter, control units cu240d-2 with encoder evaluation.
Hide thumbs Also See for SINAMICS G120D Series:
Table of Contents

Advertisement

Extended settings for faults
Parameter
You can modify the motor fault response for up to 20 different fault codes:
p2100
p2101
You can modify the acknowledgement type for up to 20 different fault codes:
p2126
p2127
You can change up to 20 different faults into an alarm, or suppress faults:
p2118
p2119
You will find details in function diagram 8075 and in the parameter description of the List
Manual.
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
Description
Setting the fault number for fault response
Selecting the faults for which the fault response should be changed
Setting, fault response
Setting the fault response for the selected fault
Setting the fault number for the acknowledgment mode
Selection of the faults for which the acknowledgment type should be changed
Setting, acknowledgment mode
Setting the acknowledgment type for the selected fault
1: Can only be acknowledged using POWER ON
2: IMMEDIATE acknowledgment after removing the fault cause
Setting the message number for the message type
Selection of the message for which the message type should be changed
Setting the message type
Setting the message type for the selected fault
1: Fault
2: Alarm
3: No message
Alarms, faults and system messages
10.2 Faults
269