Interlocking For Transformer Bay Ab_Trafo - ABB Relion 670 Series Technical Reference Manual

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Control
11.3.11
408
Name
Type
QB7_EX2
BOOLEAN
QB7_EX3
BOOLEAN
QB7_EX4
BOOLEAN
Table 236:
ABC_LINE Output signals
Name
Type
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB9REL
BOOLEAN
QB9ITL
BOOLEAN
QB1REL
BOOLEAN
QB1ITL
BOOLEAN
QB2REL
BOOLEAN
QB2ITL
BOOLEAN
QB7REL
BOOLEAN
QB7ITL
BOOLEAN
QC1REL
BOOLEAN
QC1ITL
BOOLEAN
QC2REL
BOOLEAN
QC2ITL
BOOLEAN
QC9REL
BOOLEAN
QC9ITL
BOOLEAN
QB1OPTR
BOOLEAN
QB1CLTR
BOOLEAN
QB2OPTR
BOOLEAN
QB2CLTR
BOOLEAN
QB7OPTR
BOOLEAN
QB7CLTR
BOOLEAN
QB12OPTR
BOOLEAN
QB12CLTR
BOOLEAN
VPQB1TR
BOOLEAN
VPQB2TR
BOOLEAN
VPQB7TR
BOOLEAN
VPQB12TR
BOOLEAN

Interlocking for transformer bay AB_TRAFO

Default
Description
0
External condition for apparatus QB7
0
External condition for apparatus QB7
0
External condition for apparatus QB7
Description
Closing of QA1 is allowed
Closing of QA1 is forbidden
Switching of QB9 is allowed
Switching of QB9 is forbidden
Switching of QB1 is allowed
Switching of QB1 is forbidden
Switching of QB2 is allowed
Switching of QB2 is forbidden
Switching of QB7 is allowed
Switching of QB7 is forbidden
Switching of QC1 is allowed
Switching of QC1 is forbidden
Switching of QC2 is allowed
Switching of QC2 is forbidden
Switching of QC9 is allowed
Switching of QC9 is forbidden
QB1 is in open position
QB1 is in closed position
QB2 is in open position
QB2 is in closed position
QB7 is in open position
QB7 is in closed position
QB1 or QB2 or both are in open position
QB1 and QB2 are not in open position
Switch status of QB1 is valid (open or closed)
Switch status of QB2 is valid (open or closed)
Switch status of QB7 is valid (open or closed)
Switch status of QB1 and QB2 are valid (open or
closed)
1MRK 505 208-UEN B
Technical reference manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb670

Table of Contents