addition to these specified in IEC 61850-8-1 standard. The list of values of the
"cause" are in order of priority. The values are available over the IEC 61850. An
output L_CAUSE on the function block for Switch controller (SCSWI), Circuit
breaker (SXCBR) and Circuit switch (SXSWI) indicates the latest value of the
error during the command.
Table 186:
Values for "cause" signal in priority order
Defined in IEC 61850
Table continues on next page
Attribute value
Description
0
no error
1
serviceError-type
2
blocked-by-switching-
hierarchy
3
select-failed
4
invalid-position
5
position-reached
6
parameter-change-in-
execution
7
step-limit
8
blocked-by-mode
9
blocked-by-process
10
blocked-by-interlocking
11
blocked-by-
synchrocheck
12
command-already-in-
execution
13
blocked-by-health
14
1-of-n-control
15
abortion-by-cancel
16
time-limit-over
17
abortion-by-trip
18
object-not-selected
19
Not in use
1MRK 505 208-UEN B
Supported
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Technical reference manual