Function Block; Input And Output Signals - ABB Relion 670 Series Technical Reference Manual

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 208-UEN B
11.2.5.3
11.2.5.4
Technical reference manual

Function block

SCSWI
BLOCK
EXE_OP
PSTO
EXE_CL
L_SEL
SELECTED
L_OPEN
RES_RQ
L_CLOSE
START_SY
AU_OPEN
POSITION
AU_CLOSE
OPENPOS
BL_CMD
CLOSEPOS
RES_GRT
POLEDISC
RES_EXT
CMD_BLK
SY_INPRO
L_CAUSE
SYNC_OK
XOUT
EN_OPEN
POS_INTR
EN_CLOSE
XPOS1
XPOS2
XPOS3
IEC05000337-2-en.vsd
IEC05000337 V2 EN
Figure 175:
SCSWI function block

Input and output signals

Table 195:
SCSWI Input signals
Name
Type
BLOCK
BOOLEAN
PSTO
INTEGER
L_SEL
BOOLEAN
L_OPEN
BOOLEAN
L_CLOSE
BOOLEAN
AU_OPEN
BOOLEAN
AU_CLOSE
BOOLEAN
BL_CMD
BOOLEAN
RES_GRT
BOOLEAN
RES_EXT
BOOLEAN
SY_INPRO
BOOLEAN
SYNC_OK
BOOLEAN
EN_OPEN
BOOLEAN
EN_CLOSE
BOOLEAN
XPOS1
GROUP
SIGNAL
XPOS2
GROUP
SIGNAL
XPOS3
GROUP
SIGNAL
Default
Description
0
Block of function
2
Operator place selection
0
Select signal from local panel
0
Open signal from local panel
0
Close signal from local panel
0
Used for local automation function
0
Used for local automation function
0
Steady signal for block of the command
0
Positive acknowledge that all reservations are
made
0
Reservation is made externally
0
Synchronizing function in progress
0
Closing is permitted at set to true by the
synchrocheck
0
Enables open operation
0
Enables close operation
-
Group signal from XCBR/XSWI per phase
-
Group signal from XCBR/XSWI per phase
-
Group signal from XCBR/XSWI per phase
Section 11
Control
337

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb670

Table of Contents