ABB Relion 670 Series Technical Reference Manual page 294

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 9
Multipurpose protection
Name
IMin2
tMin_OC2
VCntrlMode_OC2
VDepMode_OC2
VDepFact_OC2
ULowLimit_OC2
UHighLimit_OC2
HarmRestr_OC2
DirMode_OC2
DirPrinc_OC2
ActLowVolt2_VM
Operation_UC1
EnBlkLowI_UC1
BlkLowCurr_UC1
StartCurr_UC1
tDef_UC1
tResetDef_UC1
HarmRestr_UC1
Operation_UC2
EnBlkLowI_UC2
BlkLowCurr_UC2
StartCurr_UC2
tDef_UC2
HarmRestr_UC2
Table continues on next page
288
Values (Range)
Unit
1 - 10000
%IB
0.00 - 6000.00
s
Voltage control
-
Input control
Volt/Input control
Off
Step
-
Slope
0.02 - 5.00
-
1.0 - 200.0
%UB
1.0 - 200.0
%UB
Off
-
On
Non-directional
-
Forward
Reverse
I&U
-
IcosPhi&U
Non-directional
-
Block
Memory
Off
-
On
Off
-
On
0 - 150
%IB
2.0 - 150.0
%IB
0.00 - 6000.00
s
0.00 - 6000.00
s
Off
-
On
Off
-
On
Off
-
On
0 - 150
%IB
2.0 - 150.0
%IB
0.00 - 6000.00
s
Off
-
On
Step
Default
1
50
0.01
0.05
-
Off
-
Step
0.01
1.00
0.1
50.0
0.1
100.0
-
Off
-
Non-directional
-
I&U
-
Non-directional
-
Off
-
Off
1
20
1.0
70.0
0.01
0.50
0.01
0.00
-
Off
-
Off
-
Off
1
20
1.0
70.0
0.01
0.50
-
Off
1MRK 505 208-UEN B
Description
Minimum operate current for step2 in %
of IBase
Minimum operate time for IEC IDMT
curves for OC2
Control mode for voltage controlled OC2
function
Voltage dependent mode OC2 (step,
slope)
Multiplying factor for I pickup when OC2
is U dependent
Voltage low limit setting OC2 in % of
Ubase
Voltage high limit setting OC2 in % of
Ubase
Enable block of OC2 by 2nd harmonic
restrain
Directional mode of OC2 (nondir,
forward,reverse)
Measuring on IandU or IcosPhiandU for
OC2
Low voltage level action for Dir_OC2
(Nodir, Blk, Mem)
Operation UC1 Off / On
Enable internal low current level blocking
for UC1
Internal low current blocking level for
UC1 in % of Ibase
Operate undercurrent level for UC1 in %
of Ibase
Independent (definitive) time delay of UC1
Reset time delay used in IEC Definite
Time curve UC1
Enable block of UC1 by 2nd harmonic
restrain
Operation UC2 Off / On
Enable internal low current level blocking
for UC2
Internal low current blocking level for
UC2 in % of Ibase
Operate undercurrent level for UC2 in %
of Ibase
Independent (definitive) time delay of UC2
Enable block of UC2 by 2nd harmonic
restrain
Technical reference manual