Table 226:
BH_LINE_B Output signals
Name
Type
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB6REL
BOOLEAN
QB6ITL
BOOLEAN
QB2REL
BOOLEAN
QB2ITL
BOOLEAN
QC1REL
BOOLEAN
QC1ITL
BOOLEAN
QC2REL
BOOLEAN
QC2ITL
BOOLEAN
QC3REL
BOOLEAN
QC3ITL
BOOLEAN
QB9REL
BOOLEAN
QB9ITL
BOOLEAN
QC9REL
BOOLEAN
QC9ITL
BOOLEAN
QB2OPTR
BOOLEAN
QB2CLTR
BOOLEAN
VPQB2TR
BOOLEAN
Table 227:
BH_CONN Input signals
Name
Type
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QB61_OP
BOOLEAN
QB61_CL
BOOLEAN
QB62_OP
BOOLEAN
QB62_CL
BOOLEAN
QC1_OP
BOOLEAN
QC1_CL
BOOLEAN
QC2_OP
BOOLEAN
QC2_CL
BOOLEAN
1QC3_OP
BOOLEAN
1QC3_CL
BOOLEAN
2QC3_OP
BOOLEAN
2QC3_CL
BOOLEAN
QB61_EX1
BOOLEAN
Table continues on next page
Description
Closing of QA1 is allowed
Closing of QA1 is forbidden
Switching of QB6 is allowed
Switching of QB6 is forbidden
Switching of QB2 is allowed
Switching of QB2 is forbidden
Switching of QC1 is allowed
Switching of QC1 is forbidden
Switching of QC2 is allowed
Switching of QC2 is forbidden
Switching of QC3 is allowed
Switching of QC3 is forbidden
Switching of QB9 is allowed
Switching of QB9 is forbidden
Switching of QC9 is allowed
Switching of QC9 is forbidden
QB2 is in open position
QB2 is in closed position
Switch status of QB2 is valid (open or closed)
Default
Description
0
QA1 is in open position
0
QA1 is in closed position
0
QB61 is in open position
0
QB61 is in closed position
0
QB62 is in open position
0
QB62 is in closed position
0
QC1 is in open position
0
QC1 is in closed position
0
QC2 is in open position
0
QC2 is in closed position
0
QC3 on line 1 is in open position
0
QC3 on line 1 is in closed position
0
QC3 on line 2 is in open position
0
QC3 on line 2 is in closed position
0
External condition for apparatus QB61