Technical Data; Event Counter Cntggio; Introduction - ABB Relion 670 Series Technical Reference Manual

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 208-UEN B
Name
Values (Range)
U2HiHiLim
U2HiLim
U2LowLim
U2LowLowLim
U2AngZeroDb
13.1.6
13.2
13.2.1
Technical reference manual
Unit
0.000 -
V
10000000000.000
0.000 -
V
10000000000.000
0.000 -
V
10000000000.000
0.000 -
V
10000000000.000
0 - 100000
m%

Technical data

Table 341:
CVMMXN technical data
Function
Frequency
Voltage
Connected current
Active power, P
Reactive power, Q
Apparent power, S
Power factor, cos (φ)

Event counter CNTGGIO

Function description
Event counter

Introduction

Event counter (CNTGGIO) has six counters which are used for storing the number
of times each counter input has been activated.
Step
Default
0.001
260000.000
0.001
240000.000
0.001
220000.000
0.001
200000.000
1
0
Range or value
(0.95-1.05) × f
r
(0.1-1.5) ×U
r
(0.2-4.0) × I
r
0.1 x U
< U < 1.5 x U
r
0.2 x I
< I < 4.0 x I
r
r
0.1 x U
< U < 1.5 x U
r
0.2 x I
< I < 4.0 x I
r
r
0.1 x U
< U < 1.5 x U
r
0.2 x I
< I < 4.0 x I
r
r
0.1 x U
< U < 1.5 x U
r
0.2 x I
< I < 4.0 x I
r
r
IEC 61850
identification
CNTGGIO
Section 13
Monitoring
Description
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Zero point clamping in 0,001% of range
Accuracy
± 2.0 mHz
± 0.5% of U
at U£U
r
± 0.5% of U at U > U
± 0.5% of I
at I £ I
r
± 0.5% of I at I > I
± 1.0% of S
at S ≤ S
r
r
± 1.0% of S at S > S
Conditions:
r
0.8 x U
< U < 1.2 U
r
0.2 x I
< I < 1.2 I
r
r
± 0.02
r
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
S00946 V1 EN
r
r
r
r
r
r
r
r
493