ABB Relion 670 Series Technical Reference Manual page 591

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 208-UEN B
Technical reference manual
Info. no.
Message
16
Autorecloser active
128
CB on by Autorecloser
130
Autorecloser blocked
Measurands
Function blocks in monitor direction for input measurands. Typically connected to
monitoring function, for example to power measurement CVMMXN.
Measurands in public range, I103Meas
Number of instances: 1
The IED reports all valid measuring types depending on connected signals.
Upper limit for measured currents, active/reactive-power is 2.4 times rated value.
Upper limit for measured voltages and frequency is 1.2 times rated value.
Info. no.
Message
148
IL1
144, 145,
IL2
148
148
IL3
147
IN, Neutral current
148
UL1
148
UL2
148
UL3
145, 146
UL1-UL2
147
UN, Neutral voltage
146, 148
P, active power
146, 148
Q, reactive power
148
f, frequency
Measurands in private range, I103MeasUsr
Number of instances: 3
FUNCTION TYPE parameter for each block in private range. Default values are
defined in private range 25 – 27. One for each instance.
INFORMATION NUMBER parameter for each block. Default value 1.
Info. no.
Message
-
Meas1
-
Meas2
-
Meas3
Table continues on next page
Station communication
Supported
Yes
Yes
Yes
Supported
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Supported
Yes
Yes
Yes
Section 15
585