Input And Output Signals; Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 208-UEN B
6.6.4
6.6.5
Table 116:
GUPPDUP Group settings (basic)
Name
Values (Range)
Operation
OpMode1
Power1
Angle1
TripDelay1
DropDelay1
OpMode2
Power2
Angle2
TripDelay2
DropDelay2
Technical reference manual

Input and output signals

Table 114:
GUPPDUP Input signals
Name
I3P
U3P
BLOCK
BLOCK1
BLOCK2
Table 115:
GUPPDUP Output signals
Name
TRIP
TRIP1
TRIP2
START
START1
START2
P
PPERCENT
Q
QPERCENT

Setting parameters

Unit
Off
-
On
Off
-
UnderPower
0.0 - 500.0
%SB
-180.0 - 180.0
Deg
0.010 - 6000.000
s
0.010 - 6000.000
s
Off
-
UnderPower
0.0 - 500.0
%SB
-180.0 - 180.0
Deg
0.010 - 6000.000
s
0.010 - 6000.000
s
Type
Default
Description
GROUP
-
Current group connection
SIGNAL
GROUP
-
Voltage group connection
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Block of stage 1
BOOLEAN
0
Block of stage 2
Type
Description
BOOLEAN
Common trip signal
BOOLEAN
Trip of stage 1
BOOLEAN
Trip of stage 2
BOOLEAN
Common start
BOOLEAN
Start of stage 1
BOOLEAN
Start of stage 2
REAL
Active Power in MW
REAL
Active power in % of SBASE
REAL
Reactive power in Mvar
REAL
Reactive power in % of SBASE
Step
Default
-
Off
-
UnderPower
0.1
1.0
0.1
0.0
0.001
1.000
0.001
0.060
-
UnderPower
0.1
1.0
0.1
0.0
0.001
1.000
0.001
0.060
Section 6
Current protection
Description
Operation Off / On
Operation mode 1
Power setting for stage 1 in % of Sbase
Angle for stage 1
Trip delay for stage 1
Drop delay for stage 1
Operation mode 2
Power setting for stage 2 in % of Sbase
Angle for stage 2
Trip delay for stage 2
Drop delay for stage 2
191