Technical data

Table 450:
TRM - Energizing quantities, rated values and limits for protection transformer
modules
Quantity
Current
Operative range
Permissive overload
Burden
Ac voltage
Operative range
Permissive overload
Burden
Frequency
*)
max. 350 A for 1 s when COMBITEST test switch is included.
Analog digital conversion module, with time
synchronization (ADM)

Introduction

The Analog/Digital module has twelve analog inputs, 2 PC-MIP slots and 1 PMC
slot. The PC-MIP slot is used for PC-MIP cards and the PMC slot for PMC cards
according to table 451. The OEM card should always be mounted on the ADM
board. The UBM connects the ADM to the transformer input module (TRM).
Table 451:
PC-MIP cards and PMC cards
PC-MIP cards
LDCM
LR-LDCM
MR-LDCM
X21-LDCM
IRIG-B
RS485

Design

The Analog digital conversion module input signals are voltage and current from
the transformer module. Shunts are used to adapt the current signals to the
Rated value
I
= 1 or 5 A
r
(0-100) x I
r
4 × I
cont.
r
*)
100 × I
for 1 s
r
< 150 mVA at I
= 5 A
r
< 20 mVA at I
= 1 A
r
U
= 110 V
r
(0–340) V
420 V cont.
450 V 10 s
< 20 mVA at 110 V
f
= 50/60 Hz
r
PMC cards
SLM
OEM 1 ch
OEM 2 ch
1MRK 505 208-UEN B
Nominal range
(0.2-40) × I
r
0.5–288 V
± 5%