Function Block; Input And Output Signals; Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Current protection
6.5.3
6.5.4
6.5.5
Table 111:
CCSRBRF Group settings (basic)
Name
Operation
IBase
FunctionMode
RetripMode
IP>
Table continues on next page
184

Function block

CCSRBRF
ISI*
BLOCK
START
CBCLD
CBALARM
CBFLT
IEC06000158_2_en.vsd
IEC06000158 V2 EN
Figure 86:
CCSRBRF function block

Input and output signals

Table 109:
CCSRBRF Input signals
Name
ISI
BLOCK
START
CBCLD
CBFLT
Table 110:
CCSRBRF Output signals
Name
TRBU
TRBU2
TRRET
CBALARM

Setting parameters

Values (Range)
Unit
Off
-
On
1 - 99999
A
Current
-
Contact
Current&Contact
Retrip Off
-
I> Check
No I> Check
5 - 200
%IB
TRBU
TRBU2
TRRET
Type
Default
Description
GROUP
-
SIGNAL
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
Type
Description
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Step
Default
-
Off
1
3000
-
Current
-
Retrip Off
1
10
1MRK 505 208-UEN B
Single phase group signal for current input
Block of function
Start of breaker failure protection
Circuit breaker closed
CB faulty, unable to trip. Back-up trip
instantaneously
Back-up trip by breaker failure protection
Second back-up trip by breaker failure protection
Retrip by breaker failure protection
Alarm for faulty circuit breaker
Description
Operation Off / On
Base setting for current level settings
Detection for trip Current/Contact/
Current&Contact
Operation mode of re-trip logic: OFF /I>
check/ No I> check
Operate level in % of IBase
Technical reference manual