ABB Relion 670 Series Technical Reference Manual page 393

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 208-UEN B
Technical reference manual
Name
Type
QB9_EX2
BOOLEAN
QB9_EX3
BOOLEAN
QB9_EX4
BOOLEAN
QB9_EX5
BOOLEAN
QB9_EX6
BOOLEAN
QB9_EX7
BOOLEAN
Table 224:
BH_LINE_A Output signals
Name
Type
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB6REL
BOOLEAN
QB6ITL
BOOLEAN
QB1REL
BOOLEAN
QB1ITL
BOOLEAN
QC1REL
BOOLEAN
QC1ITL
BOOLEAN
QC2REL
BOOLEAN
QC2ITL
BOOLEAN
QC3REL
BOOLEAN
QC3ITL
BOOLEAN
QB9REL
BOOLEAN
QB9ITL
BOOLEAN
QC9REL
BOOLEAN
QC9ITL
BOOLEAN
QB1OPTR
BOOLEAN
QB1CLTR
BOOLEAN
VPQB1TR
BOOLEAN
Table 225:
BH_LINE_B Input signals
Name
Type
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QB6_OP
BOOLEAN
QB6_CL
BOOLEAN
QB2_OP
BOOLEAN
QB2_CL
BOOLEAN
QC1_OP
BOOLEAN
Table continues on next page
Default
Description
0
External condition for apparatus QB9
0
External condition for apparatus QB9
0
External condition for apparatus QB9
0
External condition for apparatus QB9
0
External condition for apparatus QB9
0
External condition for apparatus QB9
Description
Closing of QA1 is allowed
Closing of QA1 is forbidden
Switching of QB6 is allowed
Switching of QB6 is forbidden
Switching of QB1 is allowed
Switching of QB1 is forbidden
Switching of QC1 is allowed
Switching of QC1 is forbidden
Switching of QC2 is allowed
Switching of QC2 is forbidden
Switching of QC3 is allowed
Switching of QC3 is forbidden
Switching of QB9 is allowed
Switching of QB9 is forbidden
Switching of QC9 is allowed
Switching of QC9 is forbidden
QB1 is in open position
QB1 is in closed position
Switch status of QB1 is valid (open or closed)
Default
Description
0
QA1 is in open position
0
QA1 is in closed position
0
QB6 is in open position
0
QB6 is in close position
0
QB2 is in open position
0
QB2 is in closed position
0
QC1 is in open position
Section 11
Control
387