Section 8
Frequency protection
8.1.2
8.1.3
260
of RestoreFreq, the RESTORE output is issued after the time delay
TimeDlyRestore. The design of underfrequency protection SAPTUF is
schematically described in figure 132.
Block
Comparator
U < IntBlockLevel
Voltage
Frequency
Comparator
f < StartFrequency
Comparator
f > RestoreFreq
IEC05000726 V1 EN
Figure 132:
Simplified logic diagram for SAPTUF

Function block

SAPTUF
U3P*
TRIP
BLOCK
START
BLKTRIP
RESTORE
BLKREST
BLKDMAGN
FREQ
IEC06000279_2_en.vsd
IEC06000279 V2 EN
Figure 133:
SAPTUF function block

Input and output signals

Table 159:
SAPTUF Input signals
Name
Type
U3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTRIP
BOOLEAN
BLKREST
BOOLEAN
BLOCK
OR
Time integrator
TimerOperation Mode
START
Selector
TimeDlyOperate
TRIP
TimeDlyReset
TimeDlyRestore
Default
Description
-
Voltage connection
0
Block of function
0
Blocking operate output.
0
Blocking restore output.
1MRK 505 208-UEN B
BLKDMAGN
Start
START
&
Trip
Output
Logic
TRIP
100 ms
RESTORE
en05000726.vsd
Technical reference manual