Input And Output Signals - ABB Relion 670 Series Technical Reference Manual

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Control
11.3.9.4
396
VPQB61
VPQB62
&
VPQB9
1
QB61_OP
QB62_OP
QB9_OP
VPQB9
VPVOLT
&
QB9_OP
1
VOLT_OFF
IEC04000551 V1 EN

Input and output signals

Table 229:
DB_BUS_A Input signals
Name
Type
QA1_OP
BOOLEAN
QA1_CL
BOOLEAN
QB1_OP
BOOLEAN
QB1_CL
BOOLEAN
QB61_OP
BOOLEAN
QB61_CL
BOOLEAN
QC1_OP
BOOLEAN
QC1_CL
BOOLEAN
QC2_OP
BOOLEAN
QC2_CL
BOOLEAN
QC3_OP
BOOLEAN
QC3_CL
BOOLEAN
QC11_OP
BOOLEAN
QC11_CL
BOOLEAN
EXDU_ES
BOOLEAN
QB61_EX1
BOOLEAN
QB61_EX2
BOOLEAN
QB1_EX1
BOOLEAN
QB1_EX2
BOOLEAN
Table 230:
DB_BUS_A Output signals
Name
Type
QA1CLREL
BOOLEAN
QA1CLITL
BOOLEAN
QB61REL
BOOLEAN
QB61ITL
BOOLEAN
QB1REL
BOOLEAN
Table continues on next page
QC3REL
QC3ITL
QC9REL
QC9ITL
en04000551.vsd
Default
Description
0
QA1 is in open position
0
QA1 is in closed position
0
QB1 is in open position
0
QB1 is in closed position
0
QB61 is in open position
0
QB61 is in closed position
0
QC1 is in open position
0
QC1 is in closed position
0
QC2 is in open position
0
QC2 is in closed position
0
QC3 is in open position
0
QC3 is in closed position
0
Earthing switch QC11 on busbar WA1 is in open
position
0
Earthing switch QC11 on busbar WA1 is in closed
position
0
No transm error from bay containing earthing
switch QC11
0
External condition for apparatus QB61
0
External condition for apparatus QB61
0
External condition for apparatus QB1
0
External condition for apparatus QB1
Description
Closing of QA1 is allowed
Closing of QA1 is forbidden
Switching of QB61 is allowed
Switching of QB61 is forbidden
Switching of QB1 is allowed
1MRK 505 208-UEN B
Technical reference manual