Technical Data - ABB Relion 670 Series Technical Reference Manual

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 208-UEN B
Name
Values (Range)
BCrv2
CCrv2
DCrv2
PCrv2
CrvSat2
Table 136:
UV2PTUV Non group settings (basic)
Name
Values (Range)
ConnType
7.1.6
Technical reference manual
Unit
0.50 - 100.00
-
0.0 - 1.0
-
0.000 - 60.000
-
0.000 - 3.000
-
0 - 100
%
Unit
PhN DFT
-
PhPh RMS
PhN RMS
PhPh DFT

Technical data

Table 137:
UV2PTUV technical data
Function
Operate voltage, low
and high step
Absolute hysteresis
Internal blocking
level, low and high
step
Inverse time
characteristics for
low and high step,
see table
487
Definite time delays
Minimum operate
time, inverse
characteristics
Operate time, start
function
Reset time, start
function
Critical impulse time
Impulse margin time
Step
Default
0.01
1.00
0.1
0.0
0.001
0.000
0.001
1.000
1
0
Step
Default
-
PhN DFT
Range or value
UBase
(1–100)% of
UBase
(0–100)% of
UBase
(1–100)% of
-
(0.000-60.000) s
(0.000–60.000) s
25 ms typically at 2 to 0 x U
set
25 ms typically at 0 to 2 x U
set
10 ms typically at 1.2 to 0.8 x U
15 ms typically
Voltage protection
Description
Parameter B for customer programmable
curve for step 2
Parameter C for customer
programmable curve for step 2
Parameter D for customer
programmable curve for step 2
Parameter P for customer programmable
curve for step 2
Tuning param for prog. under voltage
IDMT curve, step 2
Description
Group selector for connection type
Accuracy
± 0.5% of U
r
± 0.5% of U
r
± 0.5% of U
r
See table
487
± 0.5% ±10 ms
± 0.5% ± 10 ms
-
-
-
set
-
Section 7