ABB Relion 670 Series Technical Reference Manual page 618

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 16
Remote communication
612
Name
Type
NOMESS
BOOLEAN
ADDRERR
BOOLEAN
LNGTHERR
BOOLEAN
CRCERROR
BOOLEAN
REMCOMF
BOOLEAN
LOWLEVEL
BOOLEAN
Table 438:
LDCMRecBinStat2 Output signals
Name
Type
COMFAIL
BOOLEAN
YBIT
BOOLEAN
NOCARR
BOOLEAN
NOMESS
BOOLEAN
ADDRERR
BOOLEAN
LNGTHERR
BOOLEAN
CRCERROR
BOOLEAN
TRDELERR
BOOLEAN
SYNCERR
BOOLEAN
REMCOMF
BOOLEAN
REMGPSER
BOOLEAN
SUBSTITU
BOOLEAN
LOWLEVEL
BOOLEAN
Table 439:
LDCMRecBinStat3 Output signals
Name
Type
COMFAIL
BOOLEAN
YBIT
BOOLEAN
NOCARR
BOOLEAN
NOMESS
BOOLEAN
ADDRERR
BOOLEAN
LNGTHERR
BOOLEAN
CRCERROR
BOOLEAN
TRDELERR
BOOLEAN
Table continues on next page
1MRK 505 208-UEN B
Description
No start and stop flags identified for the incoming
message
Incoming message from a wrong terminal
Wrong length of the incoming message
Identified error by CRC check in incoming message
Remote terminal indicates problem with received
message
Low signal level on the receive link
Description
Detected error in the differential communication
Detected error in remote end with incoming
message
No carrier is detected in the incoming message
No start and stop flags identified for the incoming
message
Incoming message from a wrong terminal
Wrong length of the incoming message
Identified error by CRC check in incoming message
Transmission time is longer than permitted
Indicates when echo synchronication is used
Remote terminal indicates problem with received
message
Remote terminal indicates problem with GPS
synchronization
Link error, values are substituted
Low signal level on the receive link
Description
Detected error in the differential communication
Detected error in remote end with incoming
message
No carrier is detected in the incoming message
No start and stop flags identified for the incoming
message
Incoming message from a wrong terminal
Wrong length of the incoming message
Identified error by CRC check in incoming message
Transmission time is longer than permitted
Technical reference manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb670