Section 4
Basic IED functions
Table 50:
3PHSUM Non group settings (advanced)
Name
FreqMeasMinVal
UBase
4.14
4.14.1
4.14.2
4.14.3
4.14.4
94
Values (Range)
Unit
5 - 200
%
0.05 - 2000.00
kV

Authority status ATHSTAT

Introduction

Authority status (ATHSTAT) function is an indication function block for user log
on activity.

Principle of operation

Authority status (ATHSTAT) function informs about two events related to the IED
and the user authorization:
the fact that at least one user has tried to log on wrongly into the IED and it
was blocked (the output USRBLKED)
the fact that at least one user is logged on (the output LOGGEDON)
Whenever one of the two events occurs, the corresponding output (USRBLKED or
LOGGEDON) is activated. The output can for example, be connected on Event
(EVENT) function block for LON/SPA.The signals are also available on IEC
61850 station bus.

Function block

ATHSTAT
USRBLKED
LOGGEDON
IEC06000503-2-en.vsd
IEC06000503 V2 EN
Figure 45:
ATHSTAT function block

Output signals

Table 51:
ATHSTAT Output signals
Name
USRBLKED
LOGGEDON
Step
Default
1
10
0.05
400.00
Type
Description
BOOLEAN
At least one user is blocked by invalid password
BOOLEAN
At least one user is logged on
1MRK 505 208-UEN B
Description
Amplitude limit for frequency calculation
in % of Ubase
Base voltage
Technical reference manual