ABB Relion 670 Series Technical Reference Manual page 587

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 505 208-UEN B
Technical reference manual
Function command block in control direction with defined output signals.
Number of instances: 1
FUNCTION TYPE parameter for each block.
INFORMATION NUMBER is defined for each output signals.
Info. no.
Message
16
Auto-recloser on/off
17
Teleprotection on/off
18
Protection on/off
Function commands in control direction, user-defined, I103UserCMD
Function command blocks in control direction with user-defined output signals.
Number of instances: 4
FUNCTION TYPE parameter for each block in private range. Default values are
defined in private range 1 - 4. One for each instance.
INFORMATION NUMBER is required for each output signal. Default values are 1
- 8.
Info. no.
Message
1
Output signal 01
2
Output signal 02
3
Output signal 03
4
Output signal 04
5
Output signal 05
6
Output signal 06
7
Output signal 07
8
Output signal 08
Status
Terminal status indications in monitor direction, I103IED
Indication block for status in monitor direction with defined IED functions.
Number of instances: 1
Indication block use PARAMETER as FUNCTION TYPE.
INFORMATION NUMBER is defined for each input signals.
Station communication
Supported
Yes
Yes
Yes
Supported
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Section 15
581