Section 17
IED hardware
Table 446:
Designations for 1/1 x 19" casing with 2 TRM slots
1MRK002801-AC 6 670 1.2 PG V1 EN
17.2
17.2.1
620

Hardware modules

Overview

Table 447:
Basic modules
Module
Combined backplane module (CBM)
Universal backplane module (UBM)
Power supply module (PSM)
Numerical module (NUM)
Table continues on next page
1MRK 505 208-UEN B
Module
Rear Positions
PSM
X11
BIM, BOM,
X31 and X32 etc. to X131
SOM, IOM or
and X132
MIM
SLM
X301:A, B, C, D
LDCM, IRIG-B or
X302
RS485
LDCM or RS485
X303
OEM
X311:A, B, C, D
LDCM, RS485 or
X312, X313, X322, X323
GTM
TRM 1
X401
TRM 2
X411
Description
A backplane PCB that carries all internal signals
between modules in an IED. Only the TRM (when
included) is not connected directly to this board.
A backplane PCB that forms part of the IED
backplane with connectors for TRM (when
included), ADM etc.
Including a regulated DC/DC converter that
supplies auxiliary voltage to all static circuits.
An internal fail alarm output is available.
Module for overall application control. All
information is processed or passed through this
module, such as configuration, settings and
communication.