Section 11
Control
11.2.5.5
Table 197:
SCSWI Non group settings (basic)
Name
CtlModel
PosDependent
tSelect
tResResponse
tSynchrocheck
tSynchronizing
tExecutionFB
tPoleDiscord
11.2.6
338
Table 196:
SCSWI Output signals
Name
EXE_OP
EXE_CL
SELECTED
RES_RQ
START_SY
POSITION
OPENPOS
CLOSEPOS
POLEDISC
CMD_BLK
L_CAUSE
XOUT
POS_INTR

Setting parameters

Values (Range)
Unit
Dir Norm
-
SBO Enh
Always permitted
-
Not perm at 00/11
0.00 - 600.00
s
0.000 - 60.000
s
0.00 - 600.00
s
0.00 - 600.00
s
0.00 - 600.00
s
0.000 - 60.000
s

Circuit breaker SXCBR

Type
Description
BOOLEAN
Execute command for open direction
BOOLEAN
Execute command for close direction
BOOLEAN
Select conditions are fulfilled
BOOLEAN
Request signal to the reservation function
BOOLEAN
Starts the synchronizing function
INTEGER
Position indication
BOOLEAN
Open position indication
BOOLEAN
Closed position indication
BOOLEAN
The positions for poles L1-L3 are not equal after
a set time
BOOLEAN
Commands are blocked
INTEGER
Latest value of the error indication during command
BOOLEAN
Execution information to XCBR/XSWI
BOOLEAN
Stopped in intermediate position
Step
Default
-
SBO Enh
-
Always permitted
0.01
30.00
0.001
5.000
0.01
10.00
0.01
0.00
0.01
30.00
0.001
2.000
1MRK 505 208-UEN B
Description
Specifies control model type
Permission to operate depending on the
position
Maximum time between select and
execute signals
Allowed time from reservation request to
reservation granted
Allowed time for synchrocheck to fulfil
close conditions
Supervision time to get the signal
synchronizing in progress
Maximum time from command execution
to termination
Allowed time to have discrepancy
between the poles
Technical reference manual