ABB Relion 670 Series Technical Reference Manual page 280

Busbar protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 9
Multipurpose protection
274
the magnitude of the measured current is bigger than the set pick-up level
the phasor of the measured current is within the operating region (defined by
the relay operate angle, ROADir parameter setting; see figure 137).
RCADir
Ipickup
ROADir
Operate region
IEC05000252 V1 EN
Figure 137:
I & U directional operating principle for CVGAPC function
where:
RCADir is -75°
ROADir is 50°
The second principle, referred to as "IcosPhi&U" in the parameter setting tool,
checks that:
that the product I·cos(Φ) is bigger than the set pick-up level, where Φ is angle
between the current phasor and the mta line
that the phasor of the measured current is within the operating region (defined
by the I·cos(Φ) straight line and the relay operate angle, ROADir parameter
setting; see figure 137).
U=-3U0
I=3Io
mta line
en05000252.vsd
1MRK 505 208-UEN B
Technical reference manual