Section 11
Control
Name
Obj4DefVar
Obj10DefVar
Obj20DefVar
Obj22DefVar
Obj30DefVar
Obj32DefVar
Table 271:
MST3TCP Non group settings (advanced)
Name
AddrQueryEnbl
tApplConfTout
ApplMultFrgRes
ConfMultFrag
UREnable
UREvClassMask
Table continues on next page
438
Values (Range)
Unit
1:DIChWithoutTim
-
e
2:DIChWithTime
3:DIChWithRelTim
e
1:BO
-
2:BOStatus
1:BinCnt32
-
2:BinCnt16
5:BinCnt32WoutF
6:BinCnt16WoutF
1:BinCnt32EvWout
-
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
1:AI32Int
-
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
1:AI32IntEvWoutF
-
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT
Values (Range)
Unit
No
-
Yes
0.00 - 300.00
s
No
-
Yes
No
-
Yes
No
-
Yes
Off
-
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
Step
Default
-
3:DIChWithRelTim
e
-
2:BOStatus
-
5:BinCnt32WoutF
-
1:BinCnt32EvWou
tT
-
3:AI32IntWithoutF
-
1:AI32IntEvWoutF
Step
Default
-
Yes
0.01
10.00
-
Yes
-
Yes
-
Yes
-
Off
1MRK 505 208-UEN B
Description
Object 4, default variation
Object 10, default variation
Object 20, default variation
Object 22, default variation
Object 30, default variation
Object 32, default variation
Description
Address query enable
Application layer confim timeout
Enable application for multiple fragment
response
Confirm each multiple fragment
Unsolicited response enabled
Unsolicited response, event class mask
Technical reference manual