Co-Linear Venting - Valor LX1 Installation Manual

Hide thumbs Also See for LX1:
Table of Contents

Advertisement

Venting
Co-Linear Vent Installations
Co-linear portion of vent system may only be installed
within a solid-fuel burning fi replace and chimney.
The appliance must not be connected to a chimney fl ue
serving a separate solid-fuel burning appliance.
Requires co-axial to co-linear adapter, two lengths
of 2-ply fl exible 3-inch diameter chimney liner, both
approved for venting gas appliances.
The required fi replace dimensions and clearances are
shown in Dimensions and Location and Clearances to
Combustible Materials sections of this manual (page
8 and 13 respectively).
Fit the liners to the co-linear adapter paying attention
to inlet and exhaust as well as the minimum liner bend
radius.
Rules for Co-Linear Venting
• Min 10', max 40' vertical pipe
• Max off set 8' with liners at minimum 45° from hori-
zontal plane
• Restrictor: Use restrictor position listed in vent chart
on page 21.
Co-Axial to Co-Linear Adapters
Alternate Co-Linear to Co-Axial Conversion
Terminal Cap
10"
3" Inlet & Exhaust
Collars
Co-Linear Terminal
With...
termination or approved
10"
7-5/8" dia.
collar
Co-Linear to Co-Axial
Adapter
Flashing

Co-linear Venting

Approved co-linear
co-linear adapter and
approved co-axial
termination
Flashing
2 x 3" liners
3" minimum
bend radius
Co-axial to co-linear
adapter
Flashing Kit