Limit Settings; Current Limit; Power Limit; Frequency Limit - Vacon NX ACTIVE FRONT END II Applications Manual

Table of Contents

Advertisement

Arfiff05 Standard AFE-II
6.5

Limit Settings

6.5.1 Current Limit

Code
Parameter
P2.5.1.1
Current Limit
Output Active
P2.5.1.2
Current Limit
Input Active Current
P2.5.1.3
Limit

6.5.2 Power Limit

Code
Parameter
P 2.5.2.1
Output Power Lim
P 2.5.2.2
Input Power Lim

6.5.3 Frequency Limit

Code
Parameter
Low Frequency Trip
P 2.5.3.1
Limit
High Frequency Trip
P 2.5.3.2
Limit

6.5.4 AC Voltage Limit

Code
Parameter
Low AC Voltage Trip
P 2.5.4.1
Limit
High AC Voltage Trip
P 2.5.4.2
Limit

6.5.5 DC Voltage Limit

Code
Parameter
DC Super Vision
P2.5.5.1
Limit
High MCB Close
P2.5.5.2
Limit
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Min
Max
Unit
0
Varies
A
0
300,0
%
0
300,0
%
Min
Max
Unit
0
300,0
%
0
300,0
%
Min
Max
Unit
42
120
%
42
120
%
Min
Max
Unit
50
150
%
50
150
%
Min
Max
Unit
0
1300
Vdc
0
1300
Vdc
Default
ID
Note
Varies
107
Total current limit
Generating Active Current
150,0
1290
limit in AFE mode to grid.
Motoring active current limit
150,0
1289
in AFE mode to DC-link.
Default
ID
Note
150,0
1288
Generating power limit
150,0
1287
Motoring power limit
Default
ID
Note
80
1717
120
1716
Default
ID
Note
80
1711
120
1710
Default
ID
Note
600
1454
0
1251
vacon • 33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents