Arfiff05 Standard AFE-II
V1.1.16
Operation Hours ID1856
Run state hours

5.2.2 Fieldbus monitoring values

V1.2.1
FB Control Word
Control word from fieldbus. Below table is for bypass operation for such fieldbus board that natively
supports this or can be parameterized to bypass mode.
Signal
B00
DC Charge
B01
MCB Close Enable
B02
Quick Stop
B03
Run
Output Power Limit to
B04
Zero
Disable Power Increase.
B05
Input or Output
Input Power Limit to
B06
Zero
B07
Reset
B08
DC Voltage Ref B00
B09
DC Voltage Ref B01
B10
Fieldbus Control
B11
Watchdog
B12
FB DIN2
B13
FB DIN3
B14
FB DIN4
B15
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
ID 1160
FB Control Word ID1160
0= Open MCB.
1= Close DC charge contactor, MCB closed automatically, see
B01.
0=
Disable
Closing
Options.B0=TRUE)
1= Enable Closing of MCB (Works also for reclosing)
0= Quick Stop
1= No Quick Stop
0= AFE is stopped
1= AFE is started
0= Output Power Limit to Zero (7%)
1= Output Power Limit = P2.5.2.1
0= Disable increase of power.
1= Power limits defined by G2.5.2
0= Input Power Limit to Zero (7%)
1= Output Power Limit = P2.5.2.2
0>1 Reset fault.
B00 | B01
0 | 0 = FB Reference. P2.2.1, if not FB Control & FB Ref > 50,00 %
0 | 1 = 110 %
1 | 0 = 115 %
1 | 1 = 120 %
0= No control from fieldbus
1=Control from fieldbus
communication between fieldbus master and the drive.
Can be used to control RO or directly parameter by ID number.
G2.4.1
Can be used to control RO or directly parameter by ID number.
G2.4.1
Can be used to control RO or directly parameter by ID number.
G2.4.1
Reserved for future use.
Comment
of
MCB
(Also
opens
vacon • 21
SM
1,2,3
if
Control
3
3
1,2,3
3
3
3
1,2,3
2,3
2,3
2,3
2,3
1,2,3
1,2,3
1,2,3