Line Monitoring Opt-D7; Master/Follower - Vacon NX ACTIVE FRONT END II Applications Manual

Table of Contents

Advertisement

26 • Vacon

5.2.3 Line monitoring OPT-D7

V1.3.1
Line Voltage
The measured line voltage rms value when using the OPT-D7 option board in slot C.
V1.3.2
Line Frequency Hz
The measured line voltage frequency when using the OPT-D7 option board in slot C.
V1.3.3
Synch Error D7
An error on voltage angles between the drive and the measurement taken by OPT-D7.
-3072...+3071 = -180...180 degrees.
If the value is not near to zero when running in AFE mode, the phase order may be wrong
even if the OPT-D7 frequency is correct (Error about 2047 = 120 degree). If measurement
is after Dyn11 transformer error is usually about 512 (30,0 Degree).
V1.3.4
Line Voltage THD
V1.3.5
LineVoltageHFrms

5.2.4 Master/Follower

Here are gathered relevant signals in Master follower system.
V1.4.1
SB SystemStatus
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
V1.4. 2
Master CW
Master Drive Control Word. Master Sending, Follower receiving.
V
ID1650
ID1654
ID1659
ID1670
ID1671
ID 1601
System Bus Status Word ID1601
FALSE
Not used
Drive 1 Ready
Drive 1 Running
Drive 1 Fault
Not used
Drive 2 Ready
Drive 2 Running
Drive 2 Fault
Not used
Drive 3 Ready
Drive 3 Running
Drive 3 Fault
Not used
Drive 4 Ready
Drive 4 Running
Drive 4 Fault
ID93
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
arfiff05 Standard AFE-II
TRUE

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NX ACTIVE FRONT END II and is the answer not in the manual?

Table of Contents