Arfiff05 Standard AFE-II

8.2.3 Vacon AFE 2 Profile (3)

Signal
B00
DC Charge
B01
MCB Close Enable
B02
Quick Stop
B03
Run
Output Power Limit to
B04
Zero
Disable Power Increase.
B05
Input or Output
B06
Input Power Limit to Zero
B07
Reset
B08
DC Voltage Ref B00
B09
DC Voltage Ref B01
Fieldbus Control
B10
Watchdog
B11
B12
FB DIN2
B13
FB DIN3
B14
FB DIN4
B15
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
FB Control Word ID1160
0= Open MCB.
1= Close DC charge contactor, MCB closed automatically, see B01.
0= Disable Closing of MCB (Also opens if Control Options.B0=TRUE)
1= Enable Closing of MCB (Works also for reclosing)
0= Quick Stop
1= No Quick Stop
0= AFE is stopped
1= AFE is started
0= Output Power Limit to Zero (7%)
1= Output Power Limit = P2.5.2.1
0= Disable increase of power.
1= Power limits defined by G2.5.2
0= Input Power Limit to Zero (7%)
1= Output Power Limit = P2.5.2.2
0>1 Reset fault.
B00 | B01
0 | 0 = FB Reference. P2.2.1, if not FB Control & FB Ref > 50,00 %
0 | 1 = 110 %
1 | 0 = 115 %
1 | 1 = 120 %
0= No control from fieldbus
1=Control from fieldbus
communication between fieldbus master and the drive.
Can be used to control RO or directly parameter by ID number.
G2.4.1
Can be used to control RO or directly parameter by ID number.
G2.4.1
Can be used to control RO or directly parameter by ID number.
G2.4.1
Reserved for future use.
Comment