Master Follower; Monitoring Values 2; Monitoring Values Description; Monitoring 1 Values - Vacon NX ACTIVE FRONT END II Applications Manual

Table of Contents

Advertisement

Arfiff05 Standard AFE-II

5.1.4 Master Follower

Code
Parameter
V1.4.1
SB SystemStatus
V1.42
Master CW

5.1.5 Monitoring values 2

Code
Signal
V1.5.1
Measured temperature 1
V1.5.2
Measured temperature 2
V1.5.3
Measured temperature 3
V1.5.4
Measured temperature 4
V1.5.5
Measured temperature 5
V1.5.6
Measured temperature 6
V.1.5.7
PT-100 Temperature
5.2

Monitoring Values description

5.2.1 Monitoring 1 values

V1.1.1
DC-Link Voltage
Measured DC voltage, filtered.
V1.1.2
DC-Link Ref.
DC-Link voltage reference in Vdc.
V1.1.3
DC Voltage Ref.
Used DC Voltage reference in %
V1.1.4
DC Voltage Act.
Actual DC Voltage in %
V1.1.5
Total Current
Total current of the regenerative unit in Amperes, filtered
V1.1.6
Active Current
Active current in % of System Rated Current.
Negative value means that current is flowing to AC side from DC side i.e. regenerating.
V1.1.7
Reactive Current
Reactive current of the regenerative drive in % of System Rated Current.
Positive is Inductive current.
Negative is capacitive current.
V1.1.8
Supply Frequency
Supply frequency in ##.## Hz .The sign indicates the phase order. Updated when drive in
run state. Updated also in stop state when OPT-D7 is used or Regen Options B9 is
activated.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Unit
Form.
Unit
ID
50
51
52
69
70
71
42
Vdc
ID44
Vdc
ID25
%
ID1200
%
ID7
A
ID3
%
ID1125
%
ID1157
Hz
ID1
ID
Description
1601
93
Description
4 s filtering.
4 s filtering.
4 s filtering.
4 s filtering.
4 s filtering.
4 s filtering.
Highest temperature of OPTB8/OPTBH board. 4 s
filtering.
vacon • 19