TIENet™ 360 LaserFlow Ex™ Velocity Sensor
Section 3 Setup with Signature® flowmeter
Optical Clarity – Sense voltage detects fog on the window of the
LaserFlow Ex sensor. When the sense voltage is greater than 150
mV, the defogger is activated. The defogger is enabled from 1 to 5
minutes, depending on the severity of the fog.
Note
In locations with severe fogging potential, Teledyne ISCO rec-
ommends increasing battery capacity or monitoring the site
more frequently.
To enable Optical Clarity, select "Active". To disable Optical
Clarity, select "Passive". The default is "Active".
Remote Distance Measurement – The Remote Distance Mea-
surement options are active only when the LaserFlow Ex module
is connected to the TIENet 310 remote ultrasonic sensor
• Be sure defaults are added for integral 310 Ex ultra-
sonic level sensor.
.