MVI56E-MCMR ♦ ControlLogix Platform
Modbus Communication Module with Reduced Data Block
Although these are valid addresses, they will not work in the application. The
Master must issue a Write command to the addresses that correspond to the
R
D
array. For Modbus addresses 3x, these are considered Input
EAD
ATA
registers, and a Modbus Master does not have a function code for this type of
data.
Customizing the Memory Map
In some cases, the above memory map will not work for the application.
Sometimes a Master must read bits starting at address 0001, and must also read
a register starting at 40001. With the memory map in this example (page 80), this
is not possible, as W
accommodate this, you can customize the starting location within the module for
each device using the parameters shown below.
Parameter
Bit Input Offset
Word Input Offset
Output Offset
Holding Register Offset
Based on the configuration described above for the ModDef section of the
module and the values specified for the offset parameters, below is the Modbus
addressing map for the module.
ProSoft Technology, Inc.
D
[0] is seen as both 0001 to 0016, and 40001. To
RITE
ATA
Value
Description
0
Defines the starting address within the module for 1x
Modbus addressing. A value of 0 sets 10001 to 10016 as
address 0 in the MVI56E-MCMR module.
10
Defines the starting address within the module memory
for 3x registers.
1000
Defines the starting address within the module for 0x
coils.
1010
Defines the starting address within the module for 4x
addressing.
Configuring the MVI56E-MCMR Module
Page 81 of 223
User Manual