Start Menu - ABB TruONE ATS Installation And Operating Instruction

Automatic transfer switches
Table of Contents

Advertisement

58
Tr u O N E ® AT S , I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N

4.2.1 Start Menu

Overviews
Main Menu
Fig. 4.13
4.2.1.1 Overviews
Overviews
Analog Meters
Main Menu
Measures
Fig. 4.14
System Overview (Switch status)
Shows voltages and frequencies of both supplies and the switch position.
Supply info view
Shows voltages and frequencies of both supplies.
Temperature view
Shows the HMI, device and pole temperatures.
HMI temperature indicates ambient temperature where the ATS power panel is installed, when
HMI is mounted to door.
Device temperature indicates the temperature inside the ATS power panel.
Pole temperature indicates the temperature on the load side terminals.
Synchronization view (Enabled only when In-phase monitor is on)
Show the time to next sync, sync period.
Analog Meters
Measures
TruONE ATS
TruONE ATS
Fig. 4.13 By touching on one of Start Menu
choices, you can choose the Overviews -pages
(upper left corner), Main Menu -pages (lower left
corner), Analog Meters -pages (upper right corner)
or Measures -pages (lower right corner)
Fig. 4.14 By touching on Start Menu upper left
corner -image you can move to the Overviews
-pages, where you will find Switch status and
Supply info views, see the table below
60s
System Overview
S1
Ok
S1 Connected to Load
Load Current
393 A
G
11:06
Not Ok
S2
TruONE ATS