Tr u O N E ® AT S , I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N

3.6.2 Configuration by DIP-switches

1
Auto
config
5
6
S1 Failure
delay [s]
Lamp
test
Fig. 3.9 DIP-switches for configuration in Level 2 HMI
1
Auto config: Automatically detecting
Source 1 and Source 2 parameters.
Automatic configuration sequence is
started by setting DIP to 'Start'
position. Parameter detection is
ready when AUTO LED flashes at 5 Hz.
After this the DIP must be set to 'Ok'
position to resume normal operation.
Check power supply of the voltage
source in case the Alarm LED keeps
flashing instead of AUTO LED. This
S1
l
2
In-phase
monitor
Start
On
Ok
Off
Dropout ΔU / Δf
S1 Return
delay [min]
0
2
4
10
1
3
5
15
S1
l
7
Off
LOAD
load
test
O
S2
ll
LOAD
3
Priority
No priority
Source 1
ΔU 5% / Δf 5%
ΔU 10% / Δf 5%
ΔU 15% / Δf 10%
ΔU 20% / Δf 10%
Generator
stop delay
20
30 s
30
4 min
O
S2
ll
!
8
On
Bypass
AUTO
load
time
test
delay
indicates that system parameters
cannot be detected from the supplied
voltage.
2
In-phase monitor:
On: Enable in-phase monitor
Off: Disable in-phase monitor
3
Priority:
No priority: Application 'Two
Transformers / No Priority' selected
Source 1: Application 'S1-Transformer
/ S2-Generator' selected.
!
AUTO
4
Manual
retransfer
On
Off
9
Center
/OFF
delay
0 s
4 s
Auto
Alarm reset