3 4 O X _ 3 0 - 1 6 0 0 r e v. B / 1 S C C 3 0 3 0 1 1 M 0 2 0 1
8.2.2 Wiring of OX_800U...1600 /
busbar connections and cable lugs
Automatic
transfer
switch
OX_800U...1600_
Table 8.4 OX_800U...1600_/ bolt
size and tightening torque
General warning
The cable lug must be pushed into the oval
hole of the terminal as close as possible to the
switch pole.
Fig. 8.5 OX_800U...1600, busbar connection
Bolt
Tightening
size
torque
[Nm / lb.in]
M12
50...75 / 443...664
Automatic
transfer
switch
OX_500...800_
- Busbar
OX_800U...1600_
Table 8.5 OX_500...1600_/ cable/busbar
support with breaker or fuses (SCPD)
Fig. 8.6 OX_800U...1600, wiring / cable lugs
129
Max. distance from
switch frame to nearest
cable/busbar support
SOURCE
LOAD
[mm / in]
[mm / in]
300 / 11.8
150 / 5.9
225 / 8.9
150 / 5.9
400 / 15.7
200 / 7.8