Tr u O N E ® AT S , I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N

6. Troubleshooting

6.1 Alarms
Message
Locked, Alarm LED on
Switch not in AUTO
mode, Alarm LED on
Phases crossed
S1 undervoltage
S1 overvoltage
S1 phase missing
S1 unbalance
S1 phase rotation
S1 invalid frequency
S2 undervoltage
S2 overvoltage
S2 phase missing
S2 unbalance
S2 phase rotation
Frequency Difference
Table 6.1 Alarms-list in level 3 and 4, LCD and touch control interfaces
Lock input activated
Slide switch is in handle or lock
Phase rotation of sources 1 and 2 are
Voltage of source 1 is under the
threshold level set in parameter "Drop-
out voltage, lower threshold"
Voltage of source 1 is over the
threshold level set in parameter "Drop-
out voltage, upper threshold"
One or two phases of source 1 are
Phases of source 1 are not symmetric
Phase rotation of source 1 is different
from the value of parameter "Phase
Frequency of source 1 is out of range
set in parameters "Drop-out frequency,
upper threshold" and "Drop-out
frequency, lower threshold"
Voltage of source 2 is under the
threshold level set in parameter "Drop-
out voltage, lower threshold"
Voltage of source 2 is over the
threshold level set in parameter "Drop-
out voltage, upper threshold"
One or two phases of source 2 are
Phases of source 2 are not symmetric
Phase rotation of source 2 is different
from the value of parameter "Phase
Frequency difference of voltage
sources is greater than 3 Hz while in-
phase monitor is on
Fault
Turn slide switch into the AUTO position
position
Connect the phases of both sources in
different
Check the correlation between power
source and device configuration
Check the correlation between power
source and device configuration
missing
Connect the phases according to the
sequence"
Check the correlation between power
source and device configuration
Check the correlation between power
source and device configuration
Check the correlation between power
source and device configuration
missing
Connect the phases according to the
sequence"
Alarm is active and transfer operations
disabled as long as the frequency
difference is above the accepted level
LCD
Touch
Action
Unlock
the same order
Check the power source and
connections
Check the power source
configuration
Check the power source and
connections
Check the power source
configuration