ABB TruONE ATS Installation And Operating Instruction page 64

Automatic transfer switches
Table of Contents

Advertisement

64
Tr u O N E ® AT S , I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N
Parameters (continued)
Device Parameters (continued)
Generator Exercisers
Application
Exerciser 1 / 2 / 3 / 4
Status
Function
Duration
(hh:mm:ss)
Time
(hh:mm)
Date (month
day, year)
S1-Transformer/S2-Generator*
S2-Transformer/S1-Generator
2 Transformers/S1 Priority
2 Transformers/S2 Priority
2 Transformers/No Priority
Switch and generator functioning can be tested
automatically and also periodically by using four
independent exerciser events. Test on load
function starts the generator and transfers the
load to it. Test off load function only starts the
generator for the duration of the event.
Overlapping events are prioritized, event 1 has the
highest priority.
Disabled*
Non-periodic
Daily
Weekly
Bi-weekly
Monthly
Yearly
No Function*
Test on Load
Test off load
00:00:00...24:00:59 (00:01:00*)
Starting time of the event.
00:00*...23:59
Starting date of the event
Jan 01, 2000... (---*)
*Default
Continued on the next page